WE RICH / BULK METERING
LXG Electromagnetic Water Meter
Electromagnetic measurement for water-network applications.
DN40–DN300Diameter range
ElectromagneticMeasurement
RS485 / 4GCommunication
Product Description
LXG electromagnetic water meters provide a Q3/Q1 range up to 400, typical battery service exceeding six years, a compact low-profile design, a polymer flow tube and resin-encapsulated sensor construction. Internal-humidity alarms and an optional integrated pressure sensor support network monitoring.
Key features
- DN40–DN300
- RS485 / 4G communication
- Typical six-year battery life
Technical specifications
Technical specifications
| Category | Item | Value |
|---|---|---|
| Wetted materials | Electrodes | 316L stainless steel |
| Wetted materials | Lining | Polymer flow tube |
| Transmitter | Mounting | Integrated with sensor |
| Transmitter | Enclosure | IP68, 304 stainless steel, polyamide-glass window |
| Power | Types | Integrated 3.6 V lithium battery; or 3.6 V battery + 24 VDC |
| Power | Battery life | Typically 6 years at 0–50°C / 32–122°F, measuring every 9 seconds and transmitting remotely every 6 hours. |
| Communication | Wired protocols | RS485: Modbus / custom protocol |
| Communication | Wireless | 4G |
| Communication | Antenna options | Integrated antenna or external square antenna |
| Alerts | Monitoring | Low battery, empty pipe, excitation, reverse flow, instantaneous flow min/max, pressure min/max, temperature and humidity. |
Dimensions and weight
| Size | L (mm) | Outside diameter (mm) | H (mm) | Weight (kg) |
|---|---|---|---|---|
| DN 40 | 200 (78.7) | 150 (59.1) | 292 (115) | 11 |
| DN 50 | 200 (78.7) | 165 (65) | 300 (118.1) | 13 |
| DN 65 | 200 (78.7) | 185 (72.8) | 325 (128) | 14 |
| DN 80 | 200 (78.7) | 200 (78.7) | 337 (132.7) | 21 |
| DN 100 | 250 (98.4) | 220 (86.6) | 357 (140.6) | 21 |
| DN 125 | 250 (98.4) | 250 (98.4) | 383 (150.8) | 23 |
| DN 150 | 300 (118.1) | 285 (112.2) | 413 (162.6) | 34 |
| DN 200 | 350 (137.8) | 340 (133.9) | 459 (180.7) | 47 |
| DN 250 | 450 (177.2) | 395 (155.5) | 524 (206.3) | 65 |
| DN 300 | 500 (196.9) | 445 (175.2) | 574 (226) | 88 |
ISO 4064:2024 flow requirements — R160
| Size | in. | R | Q4 m³/h (Ugal/min) | Q3 m³/h (Ugal/min) | Q2 m³/h (Ugal/min) | Q1 m³/h (Ugal/min) |
|---|---|---|---|---|---|---|
| DN 40 | 11.5 | 160 | 331.3 (138) | 25 (110) | 0.25 (1.1) | 0.16 (0.7) |
| DN 50 | 2 | 160 | 50 (220) | 40 (176) | 0.4 (1.8) | 0.25 (1.1) |
| DN 65 | 2.5 | 160 | 78.8 (347) | 63 (277) | 0.63 (2.8) | 0.39 (1.7) |
| DN 80 | 3 | 160 | 125 (550) | 100 (440) | 1 (4.4) | 0.63 (2.8) |
| DN 100 | 4 | 160 | 200 (881) | 160 (704) | 1.6 (7) | 1 (4.4) |
| DN 125 | 5 | 160 | 312 (1374) | 250 (1101) | 2.5 (11) | 1.56 (6.9) |
| DN 150 | 6 | 160 | 500 (2201) | 400 (1761) | 4 (18) | 2.5 (11) |
| DN 200 | 8 | 160 | 787.5 (3467) | 630 (2774) | 6.3 (28) | 3.94 (17) |
| DN 250 | 10 | 160 | 1250 (5504) | 1000 (4403) | 10 (44) | 6.25 (28) |
| DN 300 | 12 | 160 | 2000 (8806) | 1600 (7045) | 16 (70) | 10 (44) |
ISO 4064:2024 flow requirements — R250
| Size | in. | R | Q4 m³/h (Ugal/min) | Q3 m³/h (Ugal/min) | Q2 m³/h (Ugal/min) | Q1 m³/h (Ugal/min) |
|---|---|---|---|---|---|---|
| DN 40 | 1.5 | 250 | 31.3 (138) | 25 (110) | 0.16 (0.7) | 0.1 (0.44) |
| DN 50 | 2 | 250 | 50 (220) | 40 (176) | 0.26 (1.1) | 0.16 (0.7) |
| DN 65 | 2.5 | 250 | 78.8 (347) | 63 (277) | 0.4 (1.8) | 0.25 (1.1) |
| DN 80 | 3 | 250 | 125 (550) | 100 (440) | 0.64 (2.8) | 0.4 (1.8) |
| DN 100 | 4 | 250 | 200 (881) | 160 (704) | 1.02 (4.5) | 0.64 (2.8) |
| DN 125 | 5 | 250 | 312 (1374) | 250 (1101) | 1.6 (7) | 1 (4.4) |
| DN 150 | 6 | 250 | 500 (2201) | 400 (1761) | 2.56 (11) | 1.6 (7) |
| DN 200 | 8 | 250 | 787.5 (3467) | 630 (2774) | 4.03 (18) | 2.52 (11) |
| DN 250 | 10 | 250 | 1250 (5504) | 1000 (4403) | 6.4 (28) | 4 (18) |
| DN 300 | 12 | 250 | 2000 (8806) | 1600 (7045) | 10.24 (45) | 6.4 (28) |
ISO 4064:2024 flow requirements — R400
| Size | in. | R | Q4 m³/h (Ugal/min) | Q3 m³/h (Ugal/min) | Q2 m³/h (Ugal/min) | Q1 m³/h (Ugal/min) |
|---|---|---|---|---|---|---|
| DN 40 | 1.5 | 400 | 31.3 (138) | 25 (110) | 0.1 (0.44) | 0.063 (0.28) |
| DN 50 | 2 | 400 | 50 (220) | 40 (176) | 0.16 (0.7) | 0.1 (0.44) |
| DN 65 | 2.5 | 400 | 78.8 (347) | 63 (277) | 0.252 (1.1) | 0.158 (0.7) |
| DN 80 | 3 | 400 | 125 (550) | 100 (440) | 0.4 (1.8) | 0.25 (1.1) |
| DN 100 | 4 | 400 | 200 (881) | 160 (704) | 0.64 (2.8) | 0.4 (1.8) |
| DN 125 | 5 | 400 | 312 (1374) | 250 (1101) | 1 (4.4) | 0.625 (2.8) |
| DN 150 | 6 | 400 | 500 (2201) | 400 (1761) | 1.6 (7) | 1 (4.4) |
| DN 200 | 8 | 400 | 787.5 (3467) | 630 (2774) | 2.52 (11) | 1.575 (6.9) |
| DN 250 | 10 | 400 | 1250 (5504) | 1000 (4403) | 4 (18) | 2.5 (11) |
| DN 300 | 12 | 400 | 2000 (8806) | 1600 (7045) | 6.4 (28) | 4 (18) |
Design and functions
- Self-adhesive moulded coils and injection-moulded guide tubes improve circuit fit, magnetic-field stability and long-term measurement consistency.
- Stamped silicon-steel magnetic plates concentrate the field while lowering energy consumption.
- The integrated lithium battery supports locations without external power. DC-powered versions retain the battery for backup during outages, with battery life extended from four to more than six years.
- The PPS flow tube avoids rubber-lining ageing associated with chloride ions.
- Flow calibration is offered with ISO17025 accreditation and ILAC MRA recognition.
- Patented resin injection removes residual air, insulates coils and secures internal parts against transport or installation vibration.
- Local and remote alarms monitor empty pipes, reverse flow and abnormal pressure, temperature or flow. Users can customise flow, pressure and temperature thresholds.
Installation requirements
- Install horizontally with the flow arrow aligned and the register facing upward.
- Flush the pipeline before installation.
- Keep the meter completely filled with water during operation.
Newsroom